Bb-electronics Network Device I-7011 Manual do Utilizador Página 41

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 64
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 40
41
I-7011, I-7018 User ManualRev:B1.0
2.20 ~AAEV
Description : Enable/Disable Calibration
Syntax : ~AAEV[CHK](cr)
~ delimiter character
AA address of setting module (00 to FF)
E command for enable/disable calibration
V 1=enable calibration, 0=disable calibration
Response : Valid Command : !AA[CHK](cr)
Invalid Command : ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
Example :
Command : $010 Receive : ?01
Perform address 01 span calibration, return it is not ready for
calibration.
Command : ~01E1 Receive : !01
Set address 01 to enable calibration, return success.
Command : $010 Receive : !01
Preform address 01 span calibration, return success.
Related Command :
Sec.2.5 $AA0, Sec.2.6 $AA1
Related Topic :
Sec.1.9 Calibration
Vista de página 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 63 64

Comentários a estes Manuais

Sem comentários